Vertiv | Liebert® GXT5™ | Installer/User Guide 67
UPS fault = The contacts switch when a UPS fault has occurred (default)
Dry contact 1 (Input)
Selects the action taken by the UPS when the input of dry-contact 1 is triggered.
Disable (default)
Battery mode shutdown = If the UPS is running on batteries and this input is triggered, the UPS
shuts down
Any mode shutdown = If this input is triggered, the UPS shuts down regardless of current operating
mode
Maintenance mode = For 16&20kVA model, If this input is triggered, it means the UPS is
in Maintenance mode.
Dry contact 2 (Input)
Selects the action taken by the UPS when the input of dry-contact 2 is triggered.
Disable (default)
Battery mode shutdown = If the UPS is running on batteries and this input is triggered, the UPS
shuts
down
Any mode shutdown = If this input is triggered, the UPS shuts down regardless of current
operating mode
Maintenance mode = For 16&20kVA model, If this input is triggered, it means the UPS is in
Maintenance mode.
Sleep mode
Allows the UPS to turn off the output on a weekly schedule. For instance, turn on every Monday at 01:00
and off every Friday at 23:00.
Enable
Disable (default)
Power on day of week
Sets the day of week to turn on the UPS. This option is only shown when sleep mode is enabled.
Sunday-Saturday (default Monday)
Sets the time of day to power on the UPS on the selected day. This option is only shown when sleep
mode is enabled.
00:00 - 23:59 (default 00:00)
Power o day of week
Sets the day of week to turn o the UPS. This option is only shown when sleep mode is enabled.
Sunday-Saturday (Default is Saturday.)
Power on time

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Liebert Vertiv GXT5 and is the answer not in the manual?

Liebert Vertiv GXT5 Specifications

General IconGeneral
Output Voltage230V
TopologyDouble Conversion Online
Frequency50/60 Hz
Operating Temperature0°C to 40°C
DimensionsVaries by model
WeightVaries by model
Form FactorRack/Tower
Battery TypeValve Regulated Lead Acid (VRLA)
Communication PortsUSB, RS-232
EfficiencyUp to 95%
Typical Recharge Time3 hours to 90%
Storage Temperature-15°C to 40°C
Humidity0% to 95% non-condensing