EasyManua.ls Logo

LSIS XEC-DR32H - Appendix 4 Instruction List; Appendix 4.1.9 System Control Function

LSIS XEC-DR32H
225 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Chapter 7 Input/Output Specifications
7.4.2 16 point DC24V input module (Sink/Source type)
Model
Specification
DC input module
XBE-DC16A XBE-DC16B
Input point 16 point
Insulation method Photo coupler insulation
Rated input voltage DC24V DC 12/24V
Rated input current
About 4
About 4/8mA
Operation voltage range
DC20.4~28.8V
(ripple rate < 5%)
DC 9.5V~30V
(ripple rate< 5%)
On Voltage/Current
DC19V or higher / 3
or
higher
DC9V or higher / 3 or higher
Off Voltage/Current
DC6V or less / 1 or less DC5V or less / 1 or less
Input resistance
About 5.6 About 2.7
Response
time
Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Mega ohmmeter
Common method 16 point / COM
Proper cable size
Stranded cable 0.3~0.75 (External diameter 2.8 or less)
Current consumption
40 (when all point On)
Operation indicator Input On, LED On
External connection method 8 pin terminal block connector + 10 pin terminal block connector
Weight 53 g
Circuit configuration No.
Contact Type
TB1 0
TB2 1
TB3 2
TB4 3
TB5 4
TB6 5
TB7 6
TB8 7
TB1 8
TB2 9
TB3 A
TB4 B
TB5 C
TB6 D
TB7 E
TB8 F
TB9 COM
TB10 COM
DC24V
Internal
circuit
R
F
0
TB1
COM
Photo coupler
Terminal block no.
TB8
TB9
R
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10
7-17

Table of Contents

Related product manuals