Chapter 7 Input/Output Specifications
7.4.2 16 point DC24V input module (Sink/Source type)
Model
Specification
DC input module
XBE-DC16A XBE-DC16B
Input point 16 point
Insulation method Photo coupler insulation
Rated input voltage DC24V DC 12/24V
Rated input current
About 4
About 4/8mA
Operation voltage range
DC20.4~28.8V
(ripple rate < 5%)
DC 9.5V~30V
(ripple rate< 5%)
On Voltage/Current
DC19V or higher / 3
or
higher
DC9V or higher / 3 or higher
Off Voltage/Current
DC6V or less / 1 or less DC5V or less / 1 or less
Input resistance
About 5.6 About 2.7
Response
time
Off On
1/3/5/10/20/70/100 (set by CPU parameter) Default: 3
On Off
Insulation pressure AC560Vrms / 3Cycle (altitude 2000m)
Insulation resistance 10 or more by Mega ohmmeter
Common method 16 point / COM
Proper cable size
Stranded cable 0.3~0.75 (External diameter 2.8 or less)
Current consumption
40 (when all point On)
Operation indicator Input On, LED On
External connection method 8 pin terminal block connector + 10 pin terminal block connector
Weight 53 g
Circuit configuration No.
Contact Type
TB1 0
TB2 1
TB3 2
TB4 3
TB5 4
TB6 5
TB7 6
TB8 7
TB1 8
TB2 9
TB3 A
TB4 B
TB5 C
TB6 D
TB7 E
TB8 F
TB9 COM
TB10 COM
DC24V
Internal
circuit
R
F
0
TB1
COM
Photo coupler
Terminal block no.
TB8
TB9
R
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
TB10