Chapter 7 Input/Output Specifications
7.5 Digital Output Module Specification
7.5.1 8 point relay output module
Model
Specification
Relay output module
XBE-RY08A
Output point 8 point
Insulation method Relay insulation
Rated load voltage / Current
DC24V 2A (Resistive load) / AC220V 2A (COSΨ = 1), 5A/COM
Min. load voltage/Current
DC5V / 1
Max. load voltage/Current AC250V, DC125V
Off leakage current 0.1 (AC220V, 60 )
Max. On/Off frequency 3,600 times/hr
Surge absorber None
Service life
Mechanical 20 millions times or more
Electrical
Rated load voltage / current 100,000 times or more
AC200V / 1.5A, AC240V / 1A (COSΨ = 0.7) 100,000 times or more
AC200V / 1A, AC240V / 0.5A (COSΨ = 0.35) 100,000 times or more
DC24V / 1A, DC100V / 0.1A (L / R = 7 ) 100,000 times or more
Response
time
Off On
10 or less
On Off
12 or less
Common method 8 point / COM
Proper cable size
Twisted pair0.3~0.75 (External diameter 2.8 or less)
Current consumption
230 (when all point On)
Operation indicator Output On, LED On
External connection method 9 point terminal block connector
Weight 80g
Circuit configuration No. Contact Type
TB1 0
TB2 1
TB3 2
TB4 3
TB5 4
TB6 5
TB7 6
TB8 7
TB9 COM
TB1
TB2
TB3
TB4
TB5
TB6
TB7
TB8
TB9
DC5V
RY
Internal
circuit
Terminal block no.
TB1
TB9
TB8
7-19