Chapter 3 General Specifications
Chapter 3 General Specifications
3.1 General Specifications
The General specification of XGB series is as below.
No. Items Specifications Related standards
1
Ambient
temperature
0 ~ 55 °C
-
2
Storage
temperature
25 ~ +70 °C
3
Ambient
humidity
5 ~ 95%RH (Non-condensing)
4
Storage
humidity
5 ~ 95%RH (Non-condensing)
5
Vibration
resistance
Occasional vibration
-
Frequency
Acceleration
Amplitude
times
IEC61131-2
5
f
<
8.4Hz
3.5mm
10 times each
directions
(X, Y and Z)
8.4
f
150Hz
9.8m/s
2
(1G)
Continuous vibration
Frequency
Acceleration
Pulse width
5
f
<
8.4Hz
1.75mm
8.4
f
150Hz
4.9m/s
2
(0.5G)
6
Shock
resistance
Peak acceleration: 147 m/s
2
(15G)
Duration: 11ms
Half-sine, 3 times each direction per each axis
7
Noise
resistance
Square wave
Impulse noise
AC: ±1,500 V
DC: ±900 V
LSIS standard
Electrostatic
discharge
4kV (Contact discharge)
IEC61131-2
IEC61000-4-2
Radiated
electromagnetic
field noise
80 ~ 1,000 MHz, 10V/m
IEC61131-2,
IEC61000-4-3
Fast
transient/bust
noise
Segment
Power
supply
module
Digital/analog input/output
communication interface
IEC61131-2
IEC61000-4-4
Voltage
2kV
1kV
8
Environment
Free from corrosive gasses and excessive dust
9
Altitude
Up to 2,000 ms
10
Pollution
degree
2 or less
11
Cooling
Air-cooling
1) IEC (International Electrotechnical Commission)
:
An international civil community that promotes international cooperation for standardization of
electric/ electro technology, publishes international standard and operates suitability assessment
system related to the above.
2) Pollution Degree
:
An index to indicate the pollution degree of used environment that determines the insulation
performance of the device. For example, pollution degree 2 means the state to occur the pollution of
non-electric conductivity generally, but the state to occur temporary electric conduction according to
the formation of dew.
Notes
3-1

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the LSIS XEC-DR32H and is the answer not in the manual?

LSIS XEC-DR32H Specifications

General IconGeneral
BrandLSIS
ModelXEC-DR32H
CategoryController
LanguageEnglish

Related product manuals