Chapter 8 Built-in High-speed Counter Function
(c) Turn ‘ON’ the high-speed counter Enable signal (CH0:%KX4160) in the program.
(d) To use additional functions of the high-speed counter, you needs to turn on the flag allowing
an operation command.
* Refer to 2. Operation Command, <8.3.1 Special K Area for High-speed Counter>
For instance, turn on %KX4165 bit if among additional functions, rotation number function is used.
(e) Upon the setting, download program and parameter to PLC.
8-29