IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-36
Table 5-31: Anti-Shock Parameter Settings
Parameter Display Function Range Default
C07-12 Anti-Shock Enables or disables the Anti-Shock
function.
0–2 0
0 Disabled Anti-Shock is disabled always.
1 Enabled Anti-Shock is enabled always.
2 Enbl, Not In
MSpd
Disables Anti-Shock if Micro-Speed is
enabled.
C07-13 Enabling Freq Anti-Shock is disabled until the output
frequency is above this setting.
0.0–60.0 Hz 6.0
C07-14 Re-Accel Delay If the operator decelerates the hoist then
re-accelerates, Anti-Shock Detection is
disabled for this period of time.
0.00–2.55 sec 0.20
C07-15 Torque Delta Torque increase required to initiate the
Anti-Shock sequence.
0–180% 10
C07-16 Detection Time Time window to detect the torque delta
(C07-15).
0.01–0.50 sec 0.30
C07-17 Smoothing Freq When the torque increase is detected, the
drive will decelerate to this frequency.
0.0–15.0 Hz 3.0
C07-18 Smoothing Decel Deceleration time once an Anti-Shock
event has been detected. Increase this
value in 0.1 sec increments if DEV faults
are occurring.
0.00–2.55 sec 0.30
C07-20 Smoothing Time Time window to satisfy the steadying delta
condition.
0.00–0.50 sec 0.20
C07-22 AlarmDisplayTime When Anti-Shock is triggered, an alarm
will display on the keypad screen for the
selected duration of time.
0–30 sec 4
C07-23 No Load Torque Any torque values below this level are
ignored. This is best described as the
torque level while hoisting with an empty
hook (no load).
0–100% 20
C07-24 Activation Torque In order for Anti-Shock to be triggered, the
torque increase is required to peak above
this percentage.
0–180% 75
C07-25 Detection Method Anti-Shock detection method. 0–2 1
0 Always Detect Anti-Shock can be continuously detected.
1 Once Per Lift After Anti-Shock is detected once during a
run, it will become disabled until the hoist
is lowered.
2 Fault on Detect The drive will fault when Anti-Shock is
detected.