IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-6
Sequence/Reference Source
B03-01 and B03-02 determine the source from where the frequency reference and RUN command
are generated.
Table 5-4: Sequence/Reference Source Parameter Settings
Parameter Display Function Range Default
B03-01 Ref Source 1 Source from where the frequency
reference is generated.
0-4 1*
0Operator Digital Operator
1 Terminals Terminals or Analog Input
• S4-IF Interface Card
• S4-I AC Digital Input Option
• S4-IO Digital Input/Output Option
• DI-A3 Digital Input Option (not used for
B03-02)
2 Serial Com Serial communication
• RS485/422 Serial Communications
(R+, R-, S+, S-)
3Option PCB Industrial Communication Option
card (Port CN5-A)
• EtherNet/IP
• Modbus TCP/IP
• PROFINET
• PROFIBUS-DP
4 Pulse Input Pulse input via Terminal RP(H06-
01)
B03-02 Run Source 1 Source from where the RUN
command is generated.
0-3 1*
0Operator Digital Operator
1 Terminals Terminals
• S4-IF Interface Card
• S4-I AC Digital Input Option
• S4-IO Digital Input/Output Option
• DI-A3 Digital Input Option (not used for
B03-02)
2 Serial Com Serial communication
• RS485/422 Serial Communications
(R+, R-, S+, S-)
3Option PCB Industrial Communication Option
card (Port CN5-A)
• EtherNet/IP
• Modbus TCP/IP
• PROFINET
• PROFIBUS-DP
* Initial value is determined by X-Press Programming (Table 4-6, 4-7, or 4-8 on pages 4-12, 4-13, and 4-14).