IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-47
C11-03 SLC Detect Torq Percentage of Output Torque
below which the enabled Slack
Cable Detection is activated-as
long as the Frequency output is
between C11-04 and C11-06, and
the delay time is between C11-05
and C11-07.
-50–100% 30 VG+
C11-04 SLC Detect Spd 1 The Frequency Output that is
required for the enabled Slack
Cable Detection to be activated. It
corresponds to Slack Cable
Detection Delay Time 1 (C11-05).
0–E01-04 Hz 2 VG+
C11-05 SLC Delay Time 1 The delay time before the enabled
Slack Cable Detection can be
activated. It corresponds to Slack
Cable Detection Speed 1
(C11-04). Prevents false outputs.
0.00–2.55 sec. 0.50 VG+
C11-06 SLC Detect Spd 2 The Frequency Output below
which the enabled Slack Cable
Detection can be activated. It
corresponds to Slack Cable
Detection Delay Time 2 (C11-07).
0–E01-04 Hz 60 VG+
C11-07 SLC Delay Time 2 The delay time before the enabled
Slack Cable Detection can be
activated. It corresponds to Slack
Cable Detection Speed 2
(C11-06). Prevents false outputs.
0.00–2.55 sec. 0.10 VG+
Parameter Display Function Range Default Model

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Magnetek Impulse G+ series 4 and is the answer not in the manual?

Magnetek Impulse G+ series 4 Specifications

General IconGeneral
BrandMagnetek
ModelImpulse G+ series 4
CategoryController
LanguageEnglish

Related product manuals