IMPULSE®•G+ & VG+ Series 4 Instruction Manual – February 2017
5-96
Table 5-79: Binary to Hexadecimal Conversion
External Fault Response Selection
It is sometimes desirable to have at least one external fault input to the drive. To properly program a
multi-function input (H01-01 to H01-08) for this purpose an external fault response must be selected.
The table below shows the possible selections for an external fault response.
Table 5-80: External Fault Selection
Binary Number
Hexadecimal
Number
Binary Number
Hexadecimal
Number
0000 0 1000 8
0001 1 1001 9
0010 2 1010 A
0011 3 1011 B
0100 4 1100 C
0101 5 1101 D
0110 6 1110 E
0111 7 1111 F
Input Level
Selection
Detection Method External Fault Action
MFDI Setting
Result
N.O.
(1)
N.C.
(1)
Always
During
Run
Ramp to
Stop
Coast to Stop
Fast
Stop
(2)
Alarm
Only
 20
 24
 28
 2C
 22
 26
 2A
 2E
 21
 25
 29
 2D
 23
 27
 2B
 2F
(1) N.O. = normally open contact; N.C. = normally closed contact
(2) Uses B05-08 timer

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Magnetek Impulse G+ series 4 and is the answer not in the manual?

Magnetek Impulse G+ series 4 Specifications

General IconGeneral
BrandMagnetek
ModelImpulse G+ series 4
CategoryController
LanguageEnglish

Related product manuals