Operational supervision
Partial load operation
A3.06.18.00
M20-M601C
en / 11.12.1997 BA000090 2/2
Ĺ
Note:
If neither a changing-over to destillate fuel nor to high-load operation is possible, an
increased contamination of the lubricating oil is to be expected!
Notes:
• The permissible exhaust gas temperature after the turbine (see A3.06.06.nn) must not be
exceeded over the entire operating range, including partial load.
• Differing rules may be applicable at partial load, to protect the entire engine, during for
instance, turbocharger failures. See A3.12.00.
• If a new engine is first operated only occasionally for several hours in a load range < 50 %, as
is some times the case when a power station is being erected, operation with destilled fuel is
strongly recommended.
• If an engine with automatic charge air control is changed over from heavy fuel to distillate fuel
operation, the setting of the charge air temperature control must not be changed.