Table 15 Input Type Selection
Type
I/PNO
Type Display
Range
Resolution
NONE
0
none
-
-
E
1
E-Tc
-200 to 1000C
0.1°C
J
2
J-tc
-200 to 1200C
K
3
K-tc
-200 to 1370C
T
4
T-tc
-200 to 400C
B
5
B-tc
450 to 1800C
1 °C
R
6
R-tc
0 to 1750°C
S
7
S-tc
0 to 1750C
N
8
n-tc
-200 to 1300°C
RTD
9
RTD
-199.9 to 850.0C
0.1°C
CU53
10
cu53
-210.0 to 210.0°C
NI120
11
NI120
-70.0 to 210.0°C
-10 to 20mV
12
-10.20mv
-1999 to 9999 Counts
1 Count
0 to 100 mV
13
0-100mv
4 to 20mAmp
14
4-20ma
0 to 20mAmp
15
0-20ma
0 to 5V
16
0-5V
1 to 5V
17
1-5V
0 to 10V
18
0-10V
Acceleration RMS
19
Acc.rms
0 50.0 g
0.1
Acceleration PK
20
Acc.pk
Acceleration PK - PK
21
Acc.p2P
Velocity RMS
22
Vel.rms
0 99.9 mm/s
Velocity PK
23
Vel.pk
Velocity PK - PK
24
Vel.p2P
Displacement PK-PK
25
Dis.p2p
0 2000 um
1
Table 16 Sub Parameters of DO(Digital Output) Configuration Mode
Sub parameters of DO(Digital Output) Configuration Mode
Data
Window
Parameter
Window
Name
Setting name and
description
Default value
Shows only if
Symbol
Symbol
AL.LH
DO.CONF
Alarm Latch
on/Off
(ON/OFF)
0 : OFF
1: ON
0
-
(AL.LH)
(DO.CONF)
do.lg
DO.CONF
DO(Digital Output)
Logic Applicable for 8
Relays (Optional),
24 Open Collectors
(Optional)
nr / fs
(Normal / Fail Safe)
0: NORMAL
1: FAIL SAFE
(For all 32
DO(Digital Output))
0 (for all 32
DO(Digital
Output)) (Relay
1-8 and Open
Collector 1-24)
Any of Digital
Output(Either
Relay or Open
Collector) is
required
(do.LG)
(DO.CONF)
do.dl
DO.CONF
DO(Digital Output)Delay
0 to 99 seconds
1 (for all 32
Any of Digital

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Masibus Automation VMS4SE and is the answer not in the manual?

Masibus Automation VMS4SE Specifications

General IconGeneral
BrandMasibus Automation
ModelVMS4SE
CategoryMonitor
LanguageEnglish