User Manual 57
VMS4SE(Vibration Monitor)
REF NO: mVMA/om/101
Issue No: 01
8. ALARM OUTPUT, CONTROL OUTPUT , DIGITAL OUTPUT AND
WATCHDOG OUTPUT OPERATION
8.1 Alarm Output Operation
ï‚· Every single channel can have maximum 3 set points. 2 for Alarm outputs(1 for Alarm 1 Set Point
and 1 for Alarm 2 Set Point) and 1 for Control Set Point, totaling 48 alarm outputs and 24 control
outputs for 24 number of channels. Control Outputs are Optional.
ï‚· 8 Relays and/or 24 Open Collectors can be used as DO(Digital Output ). All Digital Outputs are
Optional.
ï‚· Following tables shows Alarm Output , control output and digital output operation.
Table 30 Alarm 1 and Alarm 2 Momentary Alarm Logic
ALARM AL1
MOMEMTARY ALARM
(when in abnormal condition ack not pressed)
CONDITION
NORMAL
ABNORMAL
UP (O/S)
DOWN (O/S)
ACK
(2)
NORMAL
(1)
ACK
(3)
ALARM
LATCH
LAMP
OFF
FLASH
FLASH
OFF
FLASH
OFF
YES
RELAY / OPEN
COLLECTOR
OFF
ON
ON
OFF
OFF
OFF
HIGH
ALARM
LATCH
LAMP
OFF
FLASH
FLASH
OFF
OFF
OFF
ASP1
NO
RELAY / OPEN
COLLECTOR
OFF
ON
ON
OFF
OFF
OFF
TRIP
LAMP
OFF
FLASH
OFF
OFF
FLASH
OFF
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
OFF
ON
OFF
ALARM
LATCH
LAMP
OFF
FLASH
OFF
FLASH
FLASH
OFF
YES
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
ON
OFF
OFF
LOW
ALARM
LATCH
LAMP
OFF
FLASH
OFF
FLASH
OFF
OFF
ASP1
NO
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
ON
OFF
OFF
TRIP
LAMP
OFF
FLASH
OFF
OFF
FLASH
OFF
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
OFF
ON
OFF
ALARM AL2
MOMEMTARY ALARM
(when in abnormal condition ack not pressed)
CONDITION
NORMAL
ABNORMAL
UP (O/S)
DOWN (O/S)
ACK
(2)
NORMAL
(1)
ACK
(3)
ALARM
LATCH
LAMP
OFF
FLASH
FLASH
OFF
FLASH
OFF
YES
RELAY / OPEN
COLLECTOR
OFF
ON
ON
OFF
OFF
OFF
HIGH
ALARM
LATCH
LAMP
OFF
FLASH
FLASH
OFF
OFF
OFF
A\SP2
NO
RELAY / OPEN
COLLECTOR
OFF
ON
ON
OFF
OFF
OFF
TRIP
LAMP
OFF
FLASH
OFF
OFF
FLASH
OFF
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
OFF
ON
OFF
ALARM
LATCH
LAMP
OFF
FLASH
OFF
FLASH
FLASH
OFF
YES
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
ON
OFF
OFF
LOW
ALARM
LATCH
LAMP
OFF
FLASH
OFF
FLASH
OFF
OFF
ASP2
NO
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
ON
OFF
OFF
TRIP
LAMP
OFF
FLASH
OFF
OFF
FLASH
OFF
RELAY / OPEN
COLLECTOR
OFF
ON
OFF
OFF
ON
OFF

Table of Contents