10 BUFFER MEMORY ACCESS
10.1 Buffer Memory
157
10
Batch write (command: 1613)
Write data to the buffer memory of the host station (supported device).
Do not write any data in "System area" or "Write-protect area" in the buffer memory.
Writing data to the "System area" or "Write-protect area" may cause malfunction of the programmable
controller system.
Message format
The following shows the message format of the request data and response data of the command.
Request data
Response data
There is no response data for this command.
Data specified by request data
Command
Subcommand
Start address
Specify the buffer memory start address to be written. (Page 153 Start address)
Word length
Specify the word length of the buffer memory to be written. (Page 154 Word length)
Specification range: 1H to 1E0H(480)
Write data
Specify the data to be written in the buffer memory. (Page 154 Read data, write data)
Specify the access range within the range of buffer memory.
(Start address + Word length -1) Buffer memory range
ASCII code Binary code
ASCII code Binary code
Command Subcommand Start address
Word
length
Write data 1 Write data n
1
31H
6
36H
1
31H
3
33H
13
H
16
H
0
30H
0
30H
0
30H
0
30H
00
H
00
H

Table of Contents