13 SERIAL COMMUNICATION MODULE DEDICATED COMMANDS
13.1 User Frame
251
13
Register data (command: 1610)
Register user frames to C24.
For MELSEC iQ-R series, the user frame is replaced with the contents registered using module extended
parameters by powering OFF ON or switching the CPU module STOP RUN. For more information on
user frame registration using module extended parameters, refer to the following manual.
MELSEC iQ-R Serial Communication Module User's Manual (Application)
When registering a user frame with the same frame No. again, deleted the user frame first and registered
again. If it is attempted to register a user frame by specifying an already registered frame No., an error occurs
and an abnormal response is returned.
Message format
The following shows the message format of the request data and response data of the command.
Request data
Response data
There is no response data for this command.
Data specified by request data
Command
*1 For C24, an additional code is added. (Page 35 Additional code (10H))
Subcommand
Frame No.
Specify the number of user frame to be registered. (Page 247 Frame No.)
Number of registration data byte, number of frame byte
Specify the byte count of registration data within the range of 1 to 80. (Page 247 Number of registration data byte, number
of frame byte)
Registration data
Store the content of user frame data to be registered. (Page 248 Registration data)
ASCII code Binary code
*1
ASCII code Binary code
Type Setting value Registration destination
User frame 3E8H to 4AFH Flash ROM of C24
8001H to 801FH Buffer memory of C24 (addresses 1B00H to 1FF6H)
Command
Subcommand
Frame No.
Registration data
Number of
registration
data byte
Number of
frame byte
1
31H
6
36H
1
31H
0
30H
10
H
16
H
DLE
10
H
0
30H
0
30H
0
30H
0
30H
00
H
00
H

Table of Contents