EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Lock (Command: 1631)

Mitsubishi Electric MELSEC iQ-R Series
498 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 CONTROL MODULE OPERATION
11.3 Remote Password
183
11
Lock (command: 1631)
Specify the remote password to lock the module. (The module cannot communicate.)
When the command is sent to the locked module, the lock status is not changed. (The password verification is
not performed.)
Message format
The following shows the message format of the request data and response data of the command.
Request data
Response data
There is no response data for this command.
Data specified by request data
Command
Subcommand
Remote password length
Specify the number of characters of remote password. (Page 170 Remote password length)
Remote password
Specify the set remote password. (Page 170 Remote password)
ASCII code Binary code
ASCII code Binary code
Command Subcommand
Remote password
length
Remote password
1
31H
6
36H
3
33H
1
31H
31
H
16
H
0
30H
0
30H
0
30H
0
30H
00
H
00
H

Table of Contents