11 CONTROL MODULE OPERATION
11.2 Remote Operation
177
11
Remote latch clear (command: 1005)
Perform remote latch clear for the access target module.
Execute the command after changing the status of the access target module to STOP.
The remote latch clear cannot be performed when the access target CPU is in remote STOP or remote
PAUSE by other devices. The command will be terminated abnormally. Clear the remote STOP or remote
PAUSE before executing the command.
Message format
The following shows the message format of the request data and response data of the command.
Request data
Response data
There is no response data for this command.
Data specified by request data
Command
*1 For C24, the additional code is added. (Page 35 Additional code (10H))
Subcommand
Fixed value
The value is '0001H'.
Communication example
Perform remote latch clear.
Data communication in ASCII code
(Request data)
Data communication in binary code
(Request data)
ASCII code Binary code (for C24)
*1
Binary code (for E71)
ASCII code Binary code
Command Subcommand
Fixed
values
1
31H
0
30H
0
30H
5
35H
05H 10H 10H
DLE
05
H
10
H
0
30H
0
30H
0
30H
0
30H
00
H
00
H
31
H
30
H
30
H
35
H
30
H
30
H
30
H
30
H
30
H
30
H
30
H
31
H
1005 0000 0001
05
H
10
H
00
H
00
H
01
H
00
H

Table of Contents