18 COMMUNICATING USING 1E FRAMES
18.4 Read and Write Device Memory
407
18
Batch write in bit units (command: 02)
Write bit devices (X, Y, M, etc.) in 1-point units.
Message format
The following shows the message format of the request data and response data of the command.
Request data
Response data
There is no response data for this command.
Data specified by request data
Head device
Specify the head device of the bit device to be written. (Page 397 Device codes and device numbers)
Fixed value
Fixed to '0'.
Number of device points
Specify the bit device points to be written.
Specify '00H' when the number of device points is to 256 points. (Page 402 Number of device points)
Write data
Stored data for the number of device points to be written.
0 (30H): OFF
1 (31H): ON
ASCII code Binary code
Head device
Number of
device points
Fixed value Write data
0
30H
0
30H
00H