EasyManua.ls Logo

Mitsubishi Electric MELSEC iQ-R Series - Page 408

Mitsubishi Electric MELSEC iQ-R Series
498 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
406
18 COMMUNICATING USING 1E FRAMES
18.4 Read and Write Device Memory
Communication example
Read the bit devices in the CPU module with E71 mounted under the following conditions.
Head device: Y40
Number of device points: 32 points (2 bytes)
Data communication in ASCII code
(Request data)
(Response data)
Data communication in binary code
(Request data)
(Response data)
35
H
39
H
32
H
30
H
30
H
30
H
30
H
30
H
30
H
30
H
34
H
30
H
30
H
32
H
30
H
30
H
5920 000000 40
0200
Head device
Number of device points
32
H
38
H
44
H
39
H
35
H
35
H
45
H
33
H
10011101
10000010
0011111001010101
829D553E
82H
9DH 55H 3EH
Data for the number of specified device points
(Y4F) to (Y48)
(Y47) to (Y40)
(Y5F) to (Y58) (Y57) to (Y50)
40
H
00
H
00
H
00
H
20
H
59
H
02
H
00
H
Head device
Number of device points
9D
H
82
H
3E
H
55
H
10011101100000100011111001010101
82H
9DH
55H3EH
Data for the number of specified device points
(Y47) to (Y40) (Y4F) to (Y48) (Y57) to (Y50) (Y5F) to (Y58)

Table of Contents

Other manuals for Mitsubishi Electric MELSEC iQ-R Series

Related product manuals