192
12 FILE CONTROL
12.1 Execution Procedure
Procedure to create new file and write data
The procedure varies depending on types of file. Refer to procedure according to file types.
Before creating a file, secure the free space of the target memory. It can be checked and secured by an
Engineering tool.
When creation of temporary file is required
1. Create a new temporary file.
Register the file name and reserve the required capacity for the file.
The extension of the temporary file must be other than DAT, PRG, QPG, PFB, QCD, DCM, QDI, DID.
Page 220 Create new file (command: 1820)
2. Write data to the file.
For writing data, use open and close command to prohibit access from other devices.
Execute the commands in the following order.
Page 236 Open file (command: 1827)
Page 242 Write to file (command: 1829)
Page 244 Close file (command: 182A)
3. Create a file with the target file extension using the copy function.
After copying a file, delete the temporary file of the copy source as necessary.
Page 226 Copy file (command: 1824)
Page 223 Delete file (command: 1822)
When creation of temporary file is not required
1. Check for file existence.
Any of the following commands can be used.
Page 211 Read directory/file information (command: 1810)
Page 217 Search directory/file information (command: 1811)
2. Create a new file.
Register the file name to reserve the required capacity for the file.
Page 220 Create new file (command: 1820)
3. Write data to the file.
For writing data, use open and close command to prohibit access from other devices.
Execute the commands in the following order.
Page 236 Open file (command: 1827)
Page 242 Write to file (command: 1829)
Page 244 Close file (command: 182A)
File type File extension Reference
MELSEC-Q/L series MELSEC iQ-R series
Header statement file DAT Page 192 When creation of temporary file is
required
Sequence program file QPG PRG
Device comment file QCD DCM
Device initial value file QDI DID
FB file PFB
File other than above Page 192 When creation of temporary file is
not required

Table of Contents