18 COMMUNICATING USING 1E FRAMES
18.5 Read and Write Extended File Register
429
18
Communication example
Read the extended file registers directly in the CPU module with E71 mounted under the following conditions.
• Block number: No.0
• Device number: R70
• Number of device points: 4 points
■Data communication in ASCII code
(Request data)
(Response data)
■Data communication in binary code
(Request data)
(Response data)
35
H
32
H
32
H
30
H
30
H
30
H
30
H
30
H
30
H
30
H
34
H
36
H
34
H
30
H
30
H
30
H
30
H
30
H
32
H
30
H
5220 000000 462000 0004
Block No. Device number
Number of device points
31
H
32
H
33
H
34
H
38
H
37
H
36
H
35
H
30
H
31
H
33
H
46
H
30
H
30
H
32
H
30
H
1234 876501 3F
2000
Data for the number of specified device points
(R70 in No.0) (R71 in No.0) (R72 in No.0) (R73 in No.0)
04
H
00
H
46
H
00
H
00
H
00
H
20
H
52
H
Device number
Number of device points
12H34H 87H65H 01H3FH 00H20H
Data for the number of specified device points
(R70 in No.0) (R72 in No.0)
(R71 in No.0) (R73 in No.0)