APPENDICES APPENDIX
Appendix 1 Read/Write by Device Extension Specification
443
A
Data to be specified
■Extension specification
Specify the value obtained by dividing the start input/output number of an intelligent function module by 16 in hexadecimal.
• ASCII code: Specify U (55H) at the head of data. Convert the numerical value to 3-digit ASCII code (hexadecimal), and
send it from the upper digits.
• Binary code: Send 2-byte numerical values from the lower byte (L: bits 0 to 7).
Start input/output number 0010H of a module
Indirect specification of the start input/output number can also be performed by using the CPU module index
register.
Page 446 Access to index the network No. and start input/output number
■Device code and device number
Specify the following device. (Page 67 Devices)
• Module access device (G)
For the values of device codes, refer to the following section.
Page 70 Device code list
Using the index register of CPU module, the access target device number can be specified indirectly.
Page 447 Access to index the device number
Device extension specification example
Access the buffer memory (address: 1) of intelligent function module whose start input/output number is 0030H by specifying
subcommand 0080.
■Data communication in ASCII code
■Data communication in binary code
ASCII code Binary code
00
30H 30H
00
30H 30H
80
38H 30H
U0
55H 30H
03
30H 33H
00
30H 30H
00
30H 30H
01
30H 31H
00
30H 30H
0
30H
G
47H
*
2AH
00
30H 30H
0
30H
Device
code
Subcommand
Extension
specification
Device number
00
H
00
H
01
H
00
H
00
H
80
H
00
H
F8
H
00
H
AB
H
00
H
03
H
00
H
Subcommand
Device
code
Device number
Extension
specification