64
7 COMMANDS AND FUNCTIONS
7.1 Command List
Label access
Buffer memory access
Module control
Function Command Description Subcommand
Batch read
and write
Batch read
array type
labels
041A Read the values from array type labels.
Read the values in batch with specifying the consecutive array elements.
Specify the array type labels or array type elements of structure type labels.
0000 For MELSEC
iQ-R series
Batch write
array type
labels
141A Write the values to array type labels.
Write the values in batch with specifying the consecutive array elements.
Specify the array type labels or array type elements of structure type labels.
0000 For MELSEC
iQ-R series
Random read
and write
Random read
labels
041C Read values with specifying multiple labels. 0000 For MELSEC
iQ-R series
Random write
labels
141B Write values with specifying multiple labels. 0000 For MELSEC
iQ-R series
Function Command Description Subcommand
Buffer
memory
Batch read 0613 Read data from the buffer memory of the host station (supported device). 0000
Batch write 1613 Write data to the buffer memory of the host station (supported device). 0000
Intelligent
function
module
Batch read 0601 Read intelligent function module buffer memory data. 0000
Batch write 1601 Write intelligent function module buffer memory data. 0000
Function Command Description Subcommand
Remote
control
Remote RUN 1001 Perform remote RUN to the access target module. 0000
Remote STOP 1002 Perform remote STOP to the access target module. 0000
Remote
PAUSE
1003 Perform remote PAUSE to the access target module. 0000
Remote latch
clear
1005 Perform remote latch clear to the access target module. 0000
Remote
RESET
1006 Perform remote RESET to the access target module. 0000
Read CPU
model name
0101 Read model name and model code from the access target module. 0000
Remote
password
Unlock 1630 Specify a remote password to enable communications with other devices.
(Change a device from the locked state to unlocked state.)
0000
Lock 1631 Specify a remote password to disable communications with other devices.
(Change a device from the unlocked state to locked state.)
0000
Loopback test 0619 Test to check whether communications between external device and connection
station operate normally.
0000
Clear error
information
Turn indicator
LED OFF,
initialize
communication
error
information/
error code
1617 Turn OFF the error LED, and initialize communication error information and error
code.
000