EasyManuals Logo

Mitsubishi QJ71MB91 User Manual

Mitsubishi QJ71MB91
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #272 background imageLoading...
Page #272 background image
9 - 43
9.3 Program Examples for Use in MELSECNET/H Remote I/O Network
9.3.2 MODBUS(R) device assignment parameters
9
PROGRAMMING
(b) Program example for MODBUS device assignment parameter setting
The program example is shown below.
Figure 9.47 MODBUS device assignment parameter setting program example when mounted to MELSECNET/H remote I/O station
R
Device code (009D
H
)
Setting
command
Coil
assignment1
Writes set values into QJ71MB91
buffer memory with REMTO instruction
Module
READY
Initializing MODBUS device assignment
parameter setting area
Head device number (0100
H
)
Head coil number (0)
Assignment points
(512 points)
Device code (00A8
H
)
Head device number (3500)
Head input register number
(3499)
Assignment points
(5500 points)
Device code (F000
H
)
Head device number (5500
H
)
Head holding register
number (0)
Assignment points
(1024 points)
Input
register
assignment1
holding
register
assignment1
Turns ON MODBUS device assignment
parameter setting request when REMTO
instruction is normally completed.
R
Error completion of REMTO instruction
Processing fot normal completion
Processing fot error completion
*1
MODBUS device assignment
parameter setting request,
error completed
R
MODBUS device assignment
parameter setting request,
normally completed
R
Intelligent function
module switch
setting change
status