EasyManua.ls Logo

Mitsubishi QJ71MB91 - Page 289

Mitsubishi QJ71MB91
372 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
10
DEDICATED INSTRUCTIONS
10.3 Z(P).MBREQ
10 - 16
9
PROGRAMMING
10
DEDICATED
INSTRUCTIONS
11
TROUBLESHOOTINGAPPENDICESINDEX
(2) Control data
* 1 The setting side is as described below.
User : Data are set by the user before dedicated instruction execution.
System: The programmable controller CPU stores the result of dedicated instruction execution.
* 2 For function codes that can be broadcast, refer to the following:
Section 4.1
* 3 When specifying a value of 32768 (8000
H) or more in a sequence program, set the value in
hexadecimal.
Table10.10 Control data of the MBREQ instruction
Device Item Setting data
Setting
range
Setting
side
*1
(S1)+0 - Specify 0. 0User
(S1)+1
Completion
status
The status of the instruction completion is stored.
0 : Normal completion
Other than 0: Error completion (error code) ( Section 11.4.3)
-System
(S1)+2 - Specify 0. 0User
(S1)+3 Channel
Specify the target channel.
1: RS-232
2: RS-422/485
1, 2 User
(S1)+4 - Specify 0. 0User
(S1)+5
Target station
No.
Specify the station number of the target slave.
0 : Broadcast
*2
1 to 247: Slave station No.
0 to 247 User
(S1)+6 - Specify 0. 0User
(S1)+7
Response
monitoring
timer value/
Broadcast
delay value
[Response monitoring timer value (Target station No. is 1 to 247)]
Specify the time for monitoring a response from the target device (slave).
(Unit: 10ms)
0 : 30 seconds
2 to 65535: Set value (Response monitoring timer value = set value x 10ms)
[Broadcast delay value (Target station No. is 0)]
Specify the wait time after broadcast transmission. (Unit: 10ms)
0 : 400ms
2 to 65535: Set value (Broadcast delay value = set value x 10ms)
For details on the Response monitoring timer value/Broadcast delay value,
refer to the following.
Section 7.2.1 (4)
0
2 to 65535
*3
User

Table of Contents

Related product manuals