(1) Automatic communication parameter error code storage area
When an error occurs with the Automatic communication parameter setting request/
Automatic communication start request (Y4/YC) ON, the corresponding error code is 
stored in this area.
(a) Storage timing
The error code is stored when the Automatic communication parameter setting, 
error completed (X5/XD) turns ON.
(b) Clear timing
The error code is cleared when the Automatic communication parameter setting, 
normally completed (X4/XC) signal turns ON. 
(2) Automatic communication parameter setting result storage area
When an automatic communication parameter error occurs with the Automatic 
communication parameter setting request/Automatic communication start request 
(Y4/YC) ON, the automatic communication parameter number corresponding to the 
error is stored in this area.
(a) Storage timing
The automatic communication parameter number is stored when the Automatic 
communication parameter setting, error completed (X5/XD) turns ON.  
(b) Clear timing
The automatic communication parameter number is cleared when the Automatic 
communication parameter setting, normally completed (X4/XC) turns ON.  
(3) MODBUS  device assignment parameter error code storage area
When an occurs with the MODBUS  device assignment parameter setting request 
(Y8) ON, the corresponding error code is stored in this area.
(a) Storage timing
The error code is stored when the MODBUS  device assignment parameter 
setting, error completed (X9) turns ON. 
(b) Clear timing
The error code is cleared when the MODBUS  device assignment parameter 
setting, normally completed (X8) turns ON. 
(4) MODBUS  device assignment parameter setting result storage area
When a MODBUS  device assignment parameter error occurs with the MODBUS  
device assignment parameter setting request (Y8) ON, the device type and assigned 
group No. of the error device are stored in this area.
(a) Storage timing
The device type and assigned group No. are stored when the MODBUS  device 
assignment parameter setting, error completed (X9) turns ON.
(b) Clear timing
The device type and assigned group No. are cleared when the MODBUS  device 
assignment parameter setting, normally completed (X8) turns ON.