4 - 3
4.1 MODBUS(R) Standard Function Support List
 
4
MODBUS(R) STANDARD FUNCTIONS
(Continued on next page)
Table4.1 MODBUS   standard function support list (continued)
Function 
code
(Sub code)
Sub-function 
code
Function Description
Accessible 
devices per 
message
Broadcast Reference
08
16 Return slave NAK count
Reads out the number of NAK 
responses to the master.
The QJ71MB91 always returns "0".
-
Section 
4.11.12
17 Return slave busy count
Reads out the number of busy 
responses to the master.
The QJ71MB91 always returns "0".
-
Section 
4.11.13
18
Return bus character 
overrun count
To the master, reads out the number of 
times the request message size 
exceeds the upper limit. 
-
Section 
4.11.14
19
Return IOP overrun 
error count
Reads the IOP overrun error counter 
value to the master.
The QJ71MB91 returns to the master 
the number of times the request 
message size exceeds the upper limit. 
(Same as the Return bus character 
overrun count)
-
Section 
4.11.15
20
Clear overrun counter 
and flag
Clears the overrun error counter and 
flag.
The QJ71MB91 clears the character 
overrun error counter value.
-
Section 
4.11.16
11 -
Get communications 
event counter
Acquires the number of messages 
whose requested processing (read/
write, diagnostics, etc.) have been 
normally completed.
Whether the action corresponding to the 
request message is normally completed 
or not can be checked.
-
Section 
4.12
12 -
Get communications 
event log
Acquires the communications event log 
of the QJ71MB91 into the master.
-
Section 
4.13
15 - Write multiple coils
Writes values (ON/OFF) to multiple 
coils.
1 to
1968 points
Section 
4.14