4 - 27
4.11 Diagnostics (FC: 08)
4.11.2 Restart communications option (sub-function code: 01)
4
MODBUS(R) STANDARD FUNCTIONS
(1) Request message format (Master   Slave)
(2) Response message format (Slave   Master)
(When completed normally)
The slave returns the request message received from the master without change.
However, if a request message is received during listen only mode, the status will only 
return to online mode and no response message will be returned.
(When completed with an error)
 * 1 Exception and error codes are stored in the buffer memory in the case of error completion.
Refer to the following for storage location, confirmation methods, and detailed contents.
 Section 11.4
Figure 4.30 Restart communications option (Request message)
Figure 4.31 Restart communications option (Exception message)
(L)
Data
(L)
Function 
code 
(08
H)
Function code
Sub-function code
Sub-function code 
(0001
H)
Clear setting of 
Communications event log
0000
H: Not clear  
FF00
H: Clear
(H)
(H)
Data
Function code
Function 
code 
(88
H)
Exception 
code*
1