8 Troubleshooting NICE7000 User Manual
- 210 -
Fault
Code
Name Possible Causes Solution Level
Err13
Power output
phase loss
The output wiring of
the main circuit is
loose.
The motor is
damaged.
Check the wiring.
Check whether the contactor on
the output side is normal.
Eliminate the motor fault.
4A
Err14
Module
overheat
The ambient
temperature is too
high.
The fan is damaged.
The air lter is
blocked.
Lower the ambient temperature.
Clear the air lter.
Replace the damaged fan.
Check whether the installation
clearance of the controller satises
the requirement.
5A
Err16
Current control
fault
1: The excitation current
deviation is too large.
2: The torque current
deviation is too large.
3: The torque limit is
exceeded for a very long
time.
1, 2, 3:
Check the circuit of the encoder.
The output MCCB becomes OFF.
The values of the current loop
parameters are too small.
Perform motor auto-tuning again if
the zero-point position is incorrect.
Reduce the load if it is too heavy.
5A
Err17
Reference
signal of
the encoder
incorrect
2: The deviation between
the Z signal position and
the absolute position is
too large.
3: The deviation
between the absolute
position angle and the
accumulative angle
exceeds 70°.
2, 3:
Check whether the encoder runs
properly.
Check whether the encoder wiring
is correct and reliable.
Check whether the PG card wiring
is correct.
Check whether the grounding of
the control cabinet and the motor
is normal.
5A
Err18
Current
detection fault
The drive control board
fails.
Contact the agent or Monarch.
5A