Redundant Systems
SUPREMA
239
US
If for non ATEX or SIL-3 relevant purposes (e.g. indicator tablet) only 1 set of output relays or driv-
ers (usually only of CAN A) are needed, then a MSO module can be attached to the not occupied
outputs (usually CAN B) directly to the MIB without use of a MUT module. The MSO module has
LED displays for the relay condition.
NOTE: In case of failure of the bus system A the external outputs are frozen to the last value.
Connection MRO 16 TS Module
If the system is redundant, the outputs of 2 MGO modules must always be evaluated
(channel A + B). The connection of up to 5 MRO 16 TS modules (40 outputs) is achieved via
1 MRC TS module. Using 20-way ribbon cables, each of the plugs, 1–5, are connected via the
8 driver outputs (channel A + B) of the MGO modules to up to 5 MRO 16 TS modules.
The 40 driver outputs of the MGO module of channel A are connected to the MRC TS modules at
Plug A using a 40-way ribbon cable via the appropriate MUT module at the rear of the rack.
The 40 driver outputs of the MGO module of channel B are connected to the MRC TS modules at
Plug B using a 40-way ribbon cable via the appropriate MUT module at the rear of the rack
Fig. 177 Connection MRO 16 TS Redundant Module
Fig. 178 Terminal Connections MRO 16 TS Module
Connection Terminals Relays Function at Position 1, (first relay block)
1-2 1, 9 1st Alarm
3-4 2, 10 2nd Alarm
5-6 3, 11 3rd Alarm
7-8 4, 12 4th Alarm
9-10 5, 13 Failure measuring value
11-12 6, 14 Horn
13-14 7, 15 Inhibit
15-16 8, 16 Power Failure