EasyManua.ls Logo

MTE HYDROCAL1005 - Page 65

MTE HYDROCAL1005
113 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HYDROCAL 1005 Manual for Installation and Operation Page 63/111
B. RS485-Bus
Using the RS485 interface it is possible to connect more the one HYDROCAL to a host. Nonetheless
it is only possible to communicate with one device at a time. The illustration below shows the sche-
matic topology.
Remark: The host (PC) must only be present once (the host connected via the TCP/IP adapter is
only present to show an alternate way to connect to the RS485 bus, as it is offered by third party
network-to-serial bridges).
HydroCal
HydroSoft
On HYDROCAL device:
Configure the device as "Bus Node"
Set an unique address for each device on the RS485 bus (1..254). Note: Communication with
HYDROCAL1002-1003 can be made right now with up to 32 units
Setup "Answer Delay" as required by the RS485 adapter in use (see also chapter: “PC RS485
Adapters” and “Answer delay)
MODBUS must be off
Configure RS485 baudrate

Table of Contents

Related product manuals