EasyManua.ls Logo

MTE HYDROCAL1005 - Page 66

MTE HYDROCAL1005
113 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HYDROCAL 1005 Manual for Installation and Operation Page 64/111
In the HydroSoft connection dialog:
Use "Connect via:" "Com-Port"
Select RS485 baudrate chosen for the devices
Check RS485
Set RS485 related checkboxes are required by the adapter (see also: “Answer delay”)
Enter correct bus address
C. Bridge
The (RS485-Bus-) bridge is an extension to access a range of HYDROCAL devices on a RS485 bus.
In this setup the host (PC) is not directly connected to the RS485 bus but is using one of the HY-
DROCAL devices as communication gateway.
The bridge functionality can be used for an RS232 or Modem primary connection as indicated by the
illustration below.
The setup of all HYDROCAL devices must be according to a standard RS485 bus setup, with one
exception. The HYDROCAL that shall serve as the communication gateway must be configured as a
(bus-) bridge.
I. Bridge Setup
HydroCal
HydroSoft

Table of Contents

Related product manuals