V10/V7.5/V5/V3.5 Installation and Operation Manual Page 2-7
Section 2 Preparation for Use and Installation Issue 3.5
Table 2-2: Input Power and Current Handling Capability
Transmitter
Ac
Supply
Mode
Input Power
(kVA)
Maximum
Phase Current
(A)
Suggested
Wire Size
(AWG)
Suggested
Breaker Rating,
Vendor #
3φ
180-264
FM
FM+HD
HD
17.4
16.2
10.1
66
61
38
2
100 A,
ABB Control Inc.
S3N100TW
3φ
Wye
312-457
FM
FM+HD
HD
17.4
16.2
10.1
66
61
38
2
100 A,
ABB Control Inc.
S3N100TW
V10
1φ
180-264
FM
FM+HD
HD
17.4
16.2
10.1
97
90
56
1
125 A,
ABB Control Inc.
S3N125TW
3φ
180-264
FM
FM+HD
HD
13.1
12.1
7.6
48
44
28
4
75 A,
ABB Control Inc.
S3N080TW
3φ
Wye
312-457
FM
FM+HD
HD
13.1
12.1
7.6
48
44
28
4
75 A,
ABB Control Inc.
S3N080TW
V7.5
1φ
180-264
FM
FM+HD
HD
13.1
12.1
7.6
73
68
42
2
100 A,
ABB Control Inc.
S3N100TW
3φ
180-264
FM
FM+HD
HD
8.7
8.1
5.1
33
31
19
6
50 A,
ABB Control Inc.
S3N050TW
3φ
Wye
312-457
FM
FM+HD
HD
8.7
8.1
5.1
33
31
19
6
50 A,
ABB Control Inc.
S3N050TW
V5
1φ
180-264
FM
FM+HD
HD
8.7
8.1
5.1
48
45
28
4
75 A,
ABB Control Inc.
S3N080TW
3φ
180-264
FM
FM+HD
HD
6.5
6.1
3.8
24
22
14
8
40 A,
ABB Control Inc.
S3N040TW
3φ
Wye
312-457
FM
FM+HD
HD
6.5
6.1
3.8
24
22
14
8
40 A,
ABB Control Inc.
S3N040TW
V3.5
1φ
180-264
FM
FM+HD
HD
6.5
6.1
3.8
37
34
21
6
50 A,
ABB Control Inc.
S3N050TW
Power and current values are based on worst-case parameters (maximum RF output power, minimum ac voltage).
Maximum inrush current (per phase) is approximately three times the maximum phase current.
Observe local electrical codes when determining wire size and circuit breakers.
Suggested wire sizes and breaker ratings based on maximum phase current for FM mode (25% over-capacity
included).