34
– Control signal (temperature or humidity signal) input via Modbus
Select “Sensor” in the steam bath settings menu, then press the <Set> key.
Adjust the parameters in the submenu “Sensor” as follows:
• “SignalSource”: “Modbus”
• “Timeout”: Timeout in seconds for signal transmission (Factory setting: 5 seconds,
Setting range: 1...600 seconds)
• “Mode”: Temp. (control via a temperature signal for steam bath operation) or Humid-
ity (control via a humidity signal for caldarium operation)
BathSettings
Light :Set
Sensor :Set
Control :Int.(P)
Fragrance :Set
P-Band :4°C
Esc Set
Settings
BathSettings:Set
Cylinder :4564
SC-System :Set
Language :English
Power Limit :100%
Esc Set
Sensor
Timeout :5s
Mode :Temp.
SignalSource:Modbus
Esc Set
SignalSource
Analog
Modbus
Modbus
Esc Set
Sensor
Timeout :5s
Mode :Temp.
SignalSource:Modbus
Esc Set
Sensor
Timeout :5s
Mode :Temp.
SignalSource:Modbus
Esc Set
Timeout
5 s
5 s
Esc Set
Mode
Temp.
Humidity
Temp.
Esc Set
Sensor
Mode :Temp.
Typ :KTY
Oset :0.0°C
SignalSource:Analog
Esc Set