How to Use the Basic Program 2. Program Change
NFS-640 Programming Manual P/N 51333:B 10/03/2003 17
Create a New Program for the Control Panel
This section covers how to use the Autoprogram option to create a new program
for the control panel. The control panel will identify all addressable detectors and
modules connected to the SLC.
To create a new program for the control panel, follow these steps:
1. Use the Clear option to clear program information from memory. For instructions on clearing
memory, refer to “How to Clear Memory (0=
CLR)” on page 16.
2. From the “Basic Program” screen, press the 1 key to start Autoprogram. While the control panel
scans the system to identify all SLC devices, Panel Circuits and NACs, it displays the following
screen:
When the autoprogram is finished identifying SLC devices, Panel Circuits and NACs, it displays a
summary screen that gives a count of all the devices it has located. Refer to the following screen for
an example of this display.
3. Press
ENTER. All devices are automatically accepted during initial autoprogramming. The
following screen displays briefly, followed by the
SYSTEM NORMAL screen.
To edit the autoprogramming default values for a point, refer to”How to Modify or Delete a Point
(2=
POINT)” on page 21.
To edit the autoprogram default values assigned to all modules and detectors during autoprogramming,
refer to “How to Change Autoprogram Default Values” on page 20.
Program Change
Password
AUTOPROGRAM PLEASE WAIT
L1:010Dets, 159Mods L2:159Dets, 159Mods
Panel Outputs: 64 Bells: 04
ACCEPT ALL DEVICES Please Wait!!!
www.PDF-Zoo.com