2. Program Change How to Use the Basic Program
40
NFS-640 Programming Manual P/N 51333:B 10/03/2003
ACS Selection Group N
This group is the same as Group A ( See Table 13 on page 35 ), with the following exceptions:
It should be selected only for TM-4s used for remote station communication.
Selection Group N follows the alarm relay for annunciation (Selection Group A annunciates
immediately).
The yellow LED of annunciator point 2 is for Alarm Silence only (in Selection Group A it is
for Signal Silenced).
ACS Selection Group O
This group is the same as Group A ( See Table 13 on page 35 ), with the following exceptions:
It should be selected for only for TM-4s used as Fire Municipal Box Trip outputs.
Selection Group O provides a “Master Box” trouble displayed at the panel.
Selection Group O follows the alarm relay for annunciation (Selection Group A annunciates
immediately).
The yellow LED of annunciator point 2 is for Alarm Silence only (in Selection Group A it is
for Signal Silenced).
www.PDF-Zoo.com

Table of Contents

Other manuals for Notifier NFS-640

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Notifier NFS-640 and is the answer not in the manual?

Notifier NFS-640 Specifications

General IconGeneral
Humidity10% to 93% non-condensing
Power Supply120/240 VAC, 50/60 Hz
Display80-character LCD
Operating Temperature0°C to 49°C (32°F to 120°F)
NAC Outputs4
Power24 VDC
CommunicationRS-485
WeightApprox. 15 lbs (without batteries)

Related product manuals