EasyManuals Logo

Omron CP1H CPU User Manual

Omron CP1H CPU
788 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #590 background imageLoading...
Page #590 background image
556
Trouble Shooting Section 9-11
03C3 --- FINS/UDP Packet
discarded
00 01 to FE
Node address
The automatic generation
(static) method was used
as the IP address conver-
sion method, so remote IP
address information in
internal memory could not
be changed.
---
03C8 --- Socket Error Arbitrary Resend the packet or the
destination node is not in
the network.
---
03D0 FLASH System setup sum value
error
Reset the value of system
setup area, Restart CPU
Unit.
Saved
0601 LIT Option Board error Arbitrary Restart the CPU Unit. If
the problem persists,
replace the Ethernet
Option Board.
Saved
0602 LIT Option Board memory error 01: Read
error
02: Write
error
04:System
setup
06:Error log
09:Identity
data
11: Mac ID
Restart the CPU Unit. If
the problem persists,
replace the Ethernet
Option Board.
Saved
(except
error log)
Error
code
ERR
LED
Meaning
Detailed error code
Correction EEPROM
1st byte 2nd byte

Table of Contents