4-3 Manually Setting Data Links
4-3-10 Reading and Data Link Tables
4-3-10 Reading and Data Link Tables
After a data link table has been created, follow the procedure below for reading it.
1 Select Network - Work Online or Network - Auto Online from the menu bar to
connect online to the target PLC.
2 Right-click the Controller Link Unit or SYSMAC LINK Unit in the Online Connection
Information Window and select Start Data Link from the popup menu. Either the
Datalink Component (Controller Link) or Datalink Component (SYSMAC LINK)
Window will be displayed.
Note: Start Data Link cannot be selected if there is not a Controller Link Unit or SYSMAC
LINK Unit mounted in the PLC that is connected online.
3 Select File - Open.
The Open Dialog Box will be displayed.
4 Select the data link table file (Sample.cl2 in this example) and then click the Open
Button.