5–27
SP ramp set value
ST (self-tuning) must be set to “OFF”.
Ă• This parameter specifies the change rate during SP ramp operation. Set the maxiĆ
mum permissible change width per unit of time (minute) as the SP ramp set value".
However, note, that when the SP ramp set value" is set to OFF", the SP ramp funcĆ
tion is disabled.
Ă• The SP ramp set value is independent of the time unit. When setting 30 per minute"
as the SP ramp set value," set the SP ramp set value" parameter to 30".
Ă• During temperature input, the decimal point position of the SP ramp set value is
dependent on the currently selected sensor, and during analog input it is dependent
on scaling.
Parameter Setting Range Unit Default
SP ramp set value OFF, 1 to 9999 EU
FĂRelated parameters
Input type" Scaling upper limit" Scaling lower limit" Decimal point" ST" (iniĆ
tial setting level)
Advanced Function Setting Level
Function
Setting
See