EasyManua.ls Logo

Omron E5GN - Page 94

Omron E5GN
132 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
E5GN
527
SP ramp set value
ST (self-tuning) must be set to OFF.
Ă This parameter specifies the change rate during SP ramp operation. Set the maxiĆ
mum permissible change width per unit of time (minute) as the SP ramp set value".
However, note, that when the SP ramp set value" is set to OFF", the SP ramp funcĆ
tion is disabled.
Ă The SP ramp set value is independent of the time unit. When setting 30 per minute"
as the SP ramp set value," set the SP ramp set value" parameter to 30".
Ă During temperature input, the decimal point position of the SP ramp set value is
dependent on the currently selected sensor, and during analog input it is dependent
on scaling.
Parameter Setting Range Unit Default
SP ramp set value OFF, 1 to 9999 EU
FĂRelated parameters
Input type" Scaling upper limit" Scaling lower limit" Decimal point" ST" (iniĆ
tial setting level)
Advanced Function Setting Level
Function
Setting
See

Table of Contents

Other manuals for Omron E5GN

Related product manuals