Appendices
A-32
NJ-series Instructions Reference Manual (W502)
Name FINS Error Error code 16#0800
Meaning An error occurred when a FINS command was sent or received.
Effects User program Continues. Operation The relevant instruction will end according to specifica-
tions.
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
An error occurred when a FINS com-
mand was sent or received.
Check the value of the ErrorIDEx out-
put variable from the instruction and
refer to the description in this manual
for the communications response
code (ErrorIDEx) with the same value
for the instruction.
Read the description of ErrorIDEx in
advance for the instruction and pro-
gram correctly.
Precautions/
Remarks
None
Name FINS Port Already in Use Error code 16#0801
Meaning The FINS port is being used.
Effects User program Continues. Operation The relevant instruction will end according to specifica-
tions. The communications output or Unit operation is not
affected.
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The FINS port is being used. Correct the program by inserting
_Port.isAvailable in a N.O. input con-
dition.
Insert _Port.isAvailable in a N.O.
input condition when you create the
program.
Precautions/
Remarks
None
Name Illegal Serial Communications Mode Error code 16#0C00
Meaning The Serial Communications Unit is not in the serial communications mode required to execute an instruction.
Effects User program Continues. Operation The relevant instruction will end according to specifica-
tions. The communications output will follow the specifica-
tions of the instruction. The operation of the Unit is not
affected.
System-defined
variables
Variable Data type Name
None --- ---
Cause and
correction
Assumed cause Correction Prevention
The serial communications port for
the Serial Communications Unit is not
set to the mode expected by the
instruction.
Change to the serial communications
mode required to execute the instruc-
tion. Or, correct the program so that it
only uses instructions that can be
executed in the current mode.
Set the Serial Communications Unit
to the serial communications mode
required to execute the instruction.
Or, correct the program so that it only
uses instructions that can be exe-
cuted in the currently set mode.
Precautions/
Remarks
None