175
Conguring the Hybrid GHP/EHP control
Setting
Setting the mode used for operation [Basic settings]
Set basic operation for Hybrid GHP/EHP control and set demand control.
4
Select the Hybrid GHP/EHP control
mode setting.
4
Item Explanation
Cost priority
control
Control so that the power/gas usage
charges are kept to a minimum based
on the unit prices set in the “Cost
settings” screen.
Energy priority
control
Control so that the energy consumed is
kept to a minimum.
EHP priority
control
The system operates so that the EHP
side is prioritised, with GHP operating
only when capacity is insufcient.
GHP priority
control
The system operates so that the GHP
side is prioritised, with EHP operating
only when capacity is insufcient.
5
Select the demand setting.
5
Item Explanation
Not set Demand control is not performed.
EHP demand GHP takes some of the load from EHP
according to the demand level.
GHP demand GHP demand control instructions are
issued according to the demand level.
The instruction value can be freely
changed in the “Gas demand settings”
screen.
Continued on next page
1
Touch [System Settings] in “Settings”.
z The “System settings” screen is displayed.
1
2
Touch [Hybrid GHP/EHP settings].
z Enter the identication number (password level 1 or 2) and
the “Hybrid GHP/EHP settings” screen is displayed.
2
3
Touch [Basic settings].
z The “Basic settings” screen is displayed.
3