95
Settings for energy saving
Energy saving
Suppressing the consumption of electricity/
gas [Demand/peak shaving settings]/[Peak cut settings*]
You can limit the electricity or gas consumed by outdoor units during the set time slot.
Attention
y Register the demand point input before making these settings. (P.89)
y Before making these settings, also cancel the demand operation settings ([No settings]) for the outdoor units in the “O/D unit information”
screen. (P.35)
3
Put a check mark in the “Select” column
(3-1), and touch [Set.] (3-2).
z The “Setting” dialogue is displayed.
3-
1
3-
2
4
Change the settings.
Item Explanation
Timer 1
Timer 2
First select either “Timer 1” or “Timer 2”,
then set the “Start time”, “End time”, and
“Demand” for each of them.
Continued on next page
1
Touch [Demand setting] in
“EnergySaving”.
1
2
Touch [Demand/peak shaving settings].
z Enter the identication number (password level 1 or 2) and
the “Demand/peak shaving settings” screen is displayed.
2
* When using gas heat pump air conditioners
When set to the 10:00 to 12:00 and 13:00 to 15:00 time slots, the
consumption of electricity/gas by the outdoor units is reduced during
those time periods.
Demand
operation
10:00 12:00 15:0013:00
High
Electricity or gas consumed
Low
Demand
operation