Conguring the system
Setting
Linked control of air conditioning units
By setting conditions for input points and output points, you can perform linked control of air conditioning
units (indoor units and outdoor units).
For example, you can make a setting so that all indoor units stop operating at the same time (output point)
in response to a re alarm going off (input point).
4
Select the input point border (4-1) and
touch [Set] (4-2).
z The “Input point settings” dialogue is displayed.
4-
1
4-
2
5
Select the input target from the list.
z Input targets include air conditioner alarms, digital input/
output devices, indoor units (individual and control groups).
5
Continued on next page
1
Touch [System Settings] in “Settings”.
z The “System settings” screen is displayed.
1
2
Touch [Event control].
z Enter the identication number (password level 1 or 2) and
the “Event control” screen is displayed.
2
3
Select an event name.
z Use to select the name to register the event.
z You can change the event names. (→ “Changing an event
name” (P.167))
3