Characters,
Factory Default
Setting Item, Function, Setting Range
[31] Step 8 SV
• Sets Step 8 SV.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available only when Program control is selected in [OUT/OFF key function].
[32]
Step 8 time
• Sets Step 8 time.
• Setting range: , or 00:00 to 99:59
If is set, Step 8 time will be held, and Fixed value control will be performed
using Step 8 SV.
Available only when Program control is selected in [OUT/OFF key function].
[33] Step 8 wait value
• Sets Step 8 wait value.
• Setting range: 0 to Converted value of 20% of the input span
DC voltage, current inputs: 0 to Converted value of 20% of scaling span (*1)
Setting the value to 0 disables Wait function.
Available only when Program control is selected in [OUT/OFF key function].
[34] Step 9 SV
• Sets Step 9 SV.
• Setting range: Scaling low limit to Scaling high limit (*1)
Available only when Program control is selected in [OUT/OFF key function].
[35]
Step 9 time
• Sets Step 9 time.
• Setting range: , or 00:00 to 99:59
If is set, Step 9 time will be held, and Fixed value control will be performed
using Step 9 SV.
Available only when Program control is selected in [OUT/OFF key function].
[36] Step 9 wait value
• Sets Step 9 wait value.
• Setting range: 0 to Converted value of 20% of the input span
DC voltage, current inputs: 0 to Converted value of 20% of scaling span (*1)
Setting the value to 0 disables Wait function.
Available only when Program control is selected in [OUT/OFF key function].
(*1) The placement of the decimal point follows the selection.