6-12 Programming Your Application
590 Series DC Digital Converter
STALL THRESHOLD
Range: 0.00 to 200.00 %
Stall comparator current feedback threshold level.
STALL TRIP DELAY
Range: 0.1 to 600.0 SECS
Stall comparator time-out delay before stall output becomes true.
STALL THRESHOLD
STALL TRIP DELAY
Comparator
CURRENT FEEDBACK
DELAY
STALL TRIP
ZERO SPD. OFFSET
OVERSPEED LEVEL
Range: 0.00 to 200.00 %
Speed feedback level for overspeed alarm
FIELD I CAL.
Range: 0.9800 to 1.1000
Trim adjustment of the motor field current to give exactly 100% at the required actual current
value (e.g. 1.5A etc.). Note: Primary field calibration is achieved by adjusting IF calibration
using SW1 - 3.
POSITION COUNT
Reserved parameter for use by Parker SSD Drives.
POSITION DIVIDER
Reserved parameter for use by Parker SSD Drives.
TERMINAL VOLTS
Refer to the DIAGNOSTICS function block description, page 6-
18.
TACH INPUT (B2)
Refer to the DIAGNOSTICS function block description, page 6-
18.
ENCODER
Refer to the DIAGNOSTICS function block description, page 6-
18.
BACK EMF
Refer to the DIAGNOSTICS function block description, page 6-
18.
STALL TRIP
Refer to the DIAGNOSTICS function block description, page 6-
18.
FIELD I FBK.
Refer to the DIAGNOSTICS function block description, page 6-
18.