4-16 Operating the Converter
590 Series DC Digital Converter
TIME-OUT IN PROGRAM STOP
SPEED SETPOINT
PROGRAM STOP LED
OFF
LED ON (PROGRAM STOP FALSE )
0%
t
SPEED DEMAND
SPEED SETPOINT
0%
t
0%
SPEED FEEDBACK
STOP ZERO SPEED
( DEFAULT 2% )
CONTACTOR WILL DROP OUT IF
SPEED FEEDBACK > STOP ZERO SPEED
WHEN PROG STOP LIMIT TIMED OUT
t
SPEED SETPOINT
t
PROG STOP LIMIT
(DEFAULT 60.0 SEC)
DRIVE RUN LED AND START CONTACTOR
DRIVE ENABLE =ENABLED
0%
DRIVE ENABLE =DISABLED
DRIVE RUN LED & START CONTACTOR
Control Signals
Speed Demand
Actual Speed
Enable
Coast Stop (B9)
This is achieved by removing 24V from Terminal B9.
The stack is automatically quenched and the contactor is opened. The motor coasts to a stop.
Note: The motor coast stop rate is dictated by the motor inertia - the drive does not control the
motion.
Standstill
Refer to Chapter 6: “Programming Your Application” -
STANDSTILL.
The Trip Condition
When a trip condition is detected, a similar stopping method to Coast Stop is used. The power
stack cannot be re-enabled until the trip condition has been cleared and successfully reset.
Refer to Chapter 7: “Trips and Fault Finding” for further details.
MMI Menu Map
1
SETUP PARAMETERS
2
STANDSTILL
STANDSTILL LOGIC
ZERO THRESHOLD