2-3
Control Features
Control
Control Circuits Fully isolated from power circuit (SELV)
Output Control
Fully controlled 3-phase thyristor bridge
Microprocessor implemented phase control extended
firing range
For use on 50 or 60Hz supplies with a frequency
compliance range of 45 to 65Hz
Phase control circuits are phase rotation insensitive
Control Action
Fully digital
Advanced PI with fully adaptive current loops for
optimum dynamic performance
Self Tuning Current Loop utilising "Autotune"
algorithm
Adjustable speed PI with integral defeat
Speed Control
By Armature Voltage feedback with IR compensation
By Encoder feedback or analog tachogenerator
Speed Range
100 to 1 typical with tachogenerator feedback
Steady State
Accuracy
0.01 % Encoder Feedback with Digital setpoint
(serial link or P3)
0.1 % Analog Tach Feedback
2 % Voltage Feedback
Absolute (0.0% error) using QUADRALOC Mk II
digital controller
Note: Long term analog accuracy is subject to
tachogenerator temperature stability.
Adjustments
All adjustments in software can be altered by on-board
pushbuttons or via serial communications. An LCD
display provides monitoring of adjustment parameters
and levels, in addition to diagnostic facilities.
Protection
High energy MOVs
Overcurrent (instantaneous)
Overcurrent (inverse time)
Field failure
Speed feedback failure
Motor overtemperature
Thyristor Stack overtemperature (Force ventilated
units)
Thyristor "Trigger" failure
Thyristor Snubber Network
Zero-speed detection
Standstill logic
Stall protection
Diagnostics
Fully computerised with first fault latch and
automatic display
Digital LCD monitoring
Full diagnostic information available on
RS422/RS485
LED circuit state indication
Table 2-1 Control Features