Programming Your Application 6-51
590 Series DC Digital Converter
SPEED LOOP
This function block contains parameters
for setting-up the speed loop. The block
is viewed in two menus on the MMI.
SETPOINTS
This MMI menu contains the setpoint
parameter reference inputs for the
function block.
MMI Menu Map
1
SETUP PARAMETERS
2
SPEED LOOP
PROP. GAIN
INT. TIME CONST.
INT. DEFEAT
ENCODER SIGN
SPEED FBK SELECT
MMI Menu Map
1
SETUP PARAMETERS
2
SPEED LOOP
3
SETPOINTS
SETPOINT 1
SIGN 2 (A3)
RATIO 2 (A3)
SETPOINT 2 (A3)
SETPOINT 3
SETPOINT 4
MAX DEMAND
MIN DEMAND
SPEED LOOP
–
OUTPUT [356]
Parameter Descriptions
PROP. GAIN
Range: ENABLED/DISABLED
Speed loop PI proportional gain adjustment.
INT. TIME CONST.
Range: 0.001 to 30.000 SECS
Speed loop PI integral gain adjustment.
INT. DEFEAT
Range: ON/OFF
Inhibits the integral part of the speed loop PI control to give proportional only control.
ENCODER SIGN
Range: POSITIVE/NEGATIVE
Since the encoder feedback cannot be reversed electrically, the signal polarity can be reversed by
the control software.
SPEED FBK SELECT
Range: See below
Four options are available:
i) Armature voltage feedback
ARM
VOLTS
ii) Analog tachogenerator feedback
ANALOG
TACH
iii) Encoder feedback
ENCODER
iv) Analog / Encoder feedback
ENCODER
/ ANALOG
SETPOINT 1
Range: -100.00 to 100.00 %
Speed Setpoint 1 (Default Setpoint Sum 1 O/P).
SIGN 2 (A3)
Range: POSITIVE/NEGATIVE
Speed Setpoint 2 Sign.