6-26 Programming Your Application
590 Series DC Digital Converter
DIGITAL OUTPUTS
This function block allows the user to
output digital parameters within the
software to other equipment. The digital
output can be configured to point to any
digital value within the software system
and output information depending upon
the status of that value.
Functional Description
Configurable Digital Outputs
INPUT
THRESHOLD
IP OP
X
|X|
1
0
%
MODULUS
DIAGNOSTIC
INVERTED
DIGOUT 1 (B5)
–
[ 97] INPUT
–
FALSE
–
[359] INVERTED
–
0.00 %
–
[195] THRESHOLD
–
TRUE
–
[ 43] MODULUS
–
–
DIGOUT 1 (B5) [ 74]
–
ON
DIGOUT 2 (B6)
–
[ 98] INPUT
–
FALSE
–
[360] INVERTED
–
0.00 %
–
[196] THRESHOLD
–
TRUE
–
[ 44] MODULUS
–
–
DIGOUT 2 (B6) [ 75]
–
ON
DIGOUT 2 (B6)
–
[ 99] INPUT
–
FALSE
–
[361] INVERTED
–
0.00 %
–
[197] THRESHOLD
–
TRUE
–
[ 45] MODULUS
–
–
DIGOUT 3 (B7) [ 76]
–
ON
MMI Menu Map
1
SYSTEM
2
CONFIGURE I/O
3
DIGITAL OUTPUTS
4
DIGOUT 1 (B5)
4
DIGOUT 2 (B6)
4
DIGOUT 3 (B7)
THRESHOLD (>)
MODULUS
SOURCE TAG
INVERTED
Parameter Descriptions
INPUT
Range: 0 to 499
(SOURCE TAG) Defines the source of the variable to control the digital output.
INVERTED
Range: TRUE/FALSE
Selects inverted output
THRESHOLD
Range: -300.00% to 300.00%
The threshold which the value must exceed to set the output to TRUE.
MODULUS
Range: TRUE/FALSE
Output set TRUE for absolute or modulus of the Tag No. value.
DIGOUT 1 (B5) to DIGOUT 3 (B7)
Refer to the DIAGNOSTICS function block description, page 6-
18.