Certification for the Converter 12-7
590 Series DC Digital Converter
Field Wiring Temperature Rating
Use 75°C copper conductors only.
Operating Ambient Temperature
For the operating ambient temperature range, refer to Chapter 11: “Technical Specifications”.
Field Wiring Terminal Markings
For the correct field wiring connections that are to be made to each terminal, refer to Chapter 3:
“Power Wiring Connections” and “Control Wiring Connections”.
Terminal Tightening Torque
Power and Control Field Wiring Terminals
For the correct tightening torque value, refer to Chapter 11: “Technical Specifications”.
Field Grounding Terminals
The field grounding terminal(s) is identified with the International Grounding Symbol
(IEC) Publication 417, Symbol 5019.
Field Terminal Kits
UL compliant Compression Lug Kits are available for the connection of power wiring for the
following Converter ratings. These lugs must be applied with the correct tooling as described in
the Installation Instructions provided with each Lug Kit.
Kit Part Number Controller
Rating (A)
Number of
Lugs
Purpose Wire Size
LA386000U035 35 5 AC/DC 8 AWG (8.4 mm
2
)
LA386000U070 70 5 AC/DC 4 AWG (21.2 mm
2
)
LA386000U110 110 3
2
AC
DC
2 AWG (33.6 mm
2
)
1/0 AWG (53.5 mm
2
)
LA386000U150 150 3
2
AC
DC
1/0 AWG (53.5 mm
2
)
3/0 AWG (85 mm
2
)
LA386000U180 180 3
2
AC
DC
3/0 AWG (85 mm
2
)
4/0 AWG (107.5 mm
2
)
LA386000U240 240 10 * AC/DC 1/0 AWG (53.5 mm
2
)
LA386000U270 270 6 *
4 *
AC
DC
1/0 AWG (53.5 mm
2
)
2/0 AWG (67.5 mm
2
)
LA386000U320 320 10* AC/DC 3/0 AWG (85mm
2
)
LA386000U450 450 6*
4*
AC
DC
250kcmil (127mm
2
)
300 kcmil (152mm
2
)
LA386000U720 720 10* AC/DC 600kcmil (304mm
2
)
* 2 cables and lugs are required per terminal.
Fuse Replacement Information
For fuse replacement information, refer to Chapter 11: “Technical Specifications”.