6-42 Programming Your Application
590 Series DC Digital Converter
RAISE/LOWER
This function block acts as an internal
motorised potentiometer (MOP).
The OUTPUT is not preserved during the
power-down of the Converter.
RAISE/LOWER
OUTPUT [264]
0.00%
0.00 %
[255] RESET VALUE
10.0 SECS
[256] INCREASE RATE
10.0 SECS
[257] DECREASE RATE
FALSE
[261] RAISE INPUT
FALSE
[262] LOWER INPUT
-100.00 %
[258] MIN VALUE
100.00 %
[259] MAX VALUE
FALSE
[307] EXTERNAL RESET
MMI Menu Map
1
SETUP PARAMETERS
2
RAISE/LOWER
RESET VALUE
INCREASE RATE
DECREASE RATE
RAISE INPUT
LOWER INPUT
MIN VALUE
MAX VALUE
EXTERNAL RESET
Parameter Descriptions
RESET VALUE
Range: -300.00 to 300.00 %
This reset value is pre-loaded directly into the output when EXTERNAL RESET is TRUE, or at
power-up. It will be clamped by min and max values.
INCREASE RATE
Range: 0.1 to 600.0 SECS
Rate of change of increasing output value.
DECREASE RATE
Range: 0.1 to 600.0 SECS
Rate of change of decreasing output value.
RAISE INPUT
Range: TRUE/FALSE
Command to raise output.
LOWER INPUT
Range: TRUE/FALSE
Command to lower output.
MIN VALUE
Range: -300.00 to 300.00 %
Minimum ramp output clamp. This is a plain clamp, not a ramped "min speed" setting.
MAX VALUE
Range: -300.00 to 300.00 %
Maximum ramp output clamp.
EXTERNAL RESET
Range: TRUE/FALSE
If EXTERNAL RESET is TRUE, the output of the Raise/Lower block is set to the RESET
VALUE.
OUTPUT
Refer to the DIAGNOSTICS function block description.